Michigan is drafting its move to the 2026 NEC. Here’s what changed nationally, mostly from NFPA’s own summary. Caveat: Michigan’s Part 8 rules amend and delete sections. Michigan’s Aug 19, 2026 draft is posted, and it can still change. Check a section there before you count on it.
Structure moved around
- Load calculations moved from Article 220 to new Article 120 in Chapter 1.
- Energy management systems moved to new Article 130.
- New Chapter 2 articles (265–270) cover systems over 1000 V ac / 1500 V dc.
- Chapter 7 was reorganized around limited-energy systems (Articles 720–750). A lot of Chapter 8 content moved into it.
Your section numbers from memory won’t match anymore. Budget time to relearn where things are.
Dwelling load calcs
- General lighting and receptacle load dropped from 3 VA/ft² to 2 VA/ft² for dwelling units. That could shrink calculated service sizes.
- But new 120.13 keeps branch-circuit counts based on 3 VA/ft², so you don’t end up with fewer circuits.
- 120.5(E) changes how continuous loads are handled.
- 120.7 lets a power control system (PCS) be factored into load calcs.
- Dryer demand factors (Table 120.54) eased for multifamily.
Outdoor GFCI and HVAC
- 210.8(F): outdoor outlets 60 A or less at dwellings need GFCI protection.
- New Exception No. 3 allows a listed Class C SPGFCI (UL 943C) for listed HVAC equipment. The old HVAC exception (No. 2) expired Sept 1, 2026.
- Industry coverage (EC&M) says the HVAC disconnect must be marked when Class C SPGFCI protection is used. See our HVAC-side explainer.
Receptacles
- 210.52(A)(5): wall or floor receptacles can’t be installed less than 24 in. below the top of a countertop or work surface. There’s an exception for receptacles in drawers.
Services (from industry coverage)
EC&M reports that 230.70(A)(1) now requires one- and two-family dwelling service disconnects in a readily accessible outdoor location, on or within sight of the house, merged with the emergency disconnect requirement. It also reports surge protection expanded to more occupancies. This comes from trade press. NFPA’s code text isn’t free to quote, so read 230.70 in the 2026 NEC. Michigan’s draft drops its own separate emergency-disconnect amendment (old 230.85) (draft).
Other
- Article 426: conductive pavement heating systems.
- Article 624: power transfer for off-road electric vehicles: golf carts, forklifts, boats.
Sources: NFPA: Key Changes in the 2026 NEC · EC&M: Key Changes to the ’26 NEC