Michigan Residential Code: stairs, decks and smoke alarms

Written by

in

Searching for the Michigan stair, deck or smoke alarm rules for a house? The code that applies to one- and two-family homes right now is the 2015 Michigan Residential Code, which is the 2015 International Residential Code (IRC) with Michigan’s changes. This page covers the Michigan changes for stairs, deck ledgers and smoke alarms, quoted from the rules in force. Look up all other details in the code book.

Which residential code applies

  • Michigan adopts the 2015 edition of the IRC by reference, minus a list of excluded sections, as the Michigan Residential Code (R 408.30500). LARA’s code books page lists the 2015 Michigan Residential Code as the current code, effective February 8, 2016 (LARA code books).
  • The 2021 IRC update is on hold. LARA says a July 7, 2025 Michigan Court of Claims order blocks it from carrying out the 2021 residential rule set while the case continues, and the 2015 versions “will remain valid and in effect” while that order is in place (LARA Currently Open Rules; 2022-16 LR tracker).

Everything below is from the Part 5 rules in force as of Nov 19, 2026 (R 408.30500–408.30547g).

Stairs: riser height and tread depth

Michigan rewrites the IRC riser and tread rules (R 408.30519, printed as R311.7.5.1 and R311.7.5.2):

  • Riser height: “The maximum riser height shall be 8 1/4 inches.” The tallest riser in a flight can’t exceed the smallest by more than 3/8 inch.
  • Tread depth: “The minimum tread depth shall be 9 inches.” The deepest tread in a flight can’t exceed the shallowest by more than 3/8 inch.
  • Winder treads: at least 10 inches deep measured 12 inches from the narrow side, and at least 6 inches deep at any point. Within a flight, winder depths at the 12-inch walk line can’t differ by more than 3/8 inch.

Michigan’s Part 5 rules don’t change the IRC’s stair width, headroom, handrail or guard sections. Those come straight from the 2015 IRC text, so check the code book for them.

Exit and interior doors

Under the same egress rule, the required exit door must be a side-hinged door at least 3 feet wide and 6 feet 8 inches high. Other exterior hinged or sliding doors must be at least 24 inches wide and 6 feet 6 inches high. Interior doors must also be at least 24 inches wide and 6 feet 6 inches high, except doors to areas under 10 square feet (R 408.30518).

Decks

  • Ledger fasteners: Michigan replaces IRC figure R507.2.1(1), which shows where lag screws and bolts go in deck ledgers and band joists (R 408.30523). Use the Michigan figure, not the one in a plain IRC book.
  • Ledger flashing: Michigan adds R507.2.4: “An approved corrosion resistant flashing as required by Section R703.8 shall be installed above the attached ledger as shown in figure R507.2.1(2) or as approved.” Figure R507.2.1(2) is also Michigan’s own version (R 408.30523a).
  • Some IRC deck items are excluded: Michigan’s adoption rule leaves out several IRC deck provisions, including table R507.2.3 and IRC figure R507.2.1(2), and puts the Michigan versions above in their place (R 408.30500).
  • Permits: a deck needs no building permit only if it meets every one of these conditions: 200 square feet or less, no more than 30 inches above grade at any point, not attached to the house or an accessory structure, not within 36 inches of either, and not serving any entry or exit door (R 408.30505, R105.2). An attached deck needs a permit.

Smoke alarms

Michigan rewrites several IRC smoke alarm sections (R 408.30546):

  • Locations (R314.3): in each sleeping room or in the immediate vicinity of the sleeping room, and on each additional story, including basements and habitable attics but not crawl spaces or uninhabitable attics. In a split level with no door between the levels, one alarm on the upper level covers the lower level if the lower level is less than one full story below.
  • Interconnection (R314.4): when more than one alarm is required in a dwelling unit, they must be interconnected so one sets off all. Listed wireless alarms that all sound together meet this. Alarms in existing areas don’t have to be interconnected.
  • Remodels and additions (R314.2.2): when permitted alterations, repairs or additions happen, or a sleeping room is added or created, the dwelling unit needs smoke alarms placed as required for new homes. The exceptions are exterior work (roofing, siding, windows, doors, adding a porch or deck) and electrical, plumbing or mechanical work.
  • Homes built before November 6, 1974 that aren’t getting permitted work need alarms in each sleeping room and on each floor level, including the basement. Battery-operated alarms are one of the allowed power sources for these homes (R314.3.2 and R314.3.3).
  • Upkeep: the owner is responsible for proper operation, testing and maintenance. In rentals, the occupant handles periodic testing and cleaning. A failed system must be repaired and working within 30 days (R314.3.3).

Carbon monoxide alarms

When work that requires a building permit happens in an existing house that has an attached garage or fuel-fired appliances, CO alarms must be added per R315.1 (R 408.30520).

What to do

  • Build stairs to Michigan’s 8 1/4-inch maximum riser and 9-inch minimum tread. Check everything else on stairs against the 2015 IRC text.
  • Use Michigan’s ledger fastener figure and flash every attached ledger. Pull a permit for any attached deck.
  • On any permitted remodel or addition, apart from the exempt exterior and trade work, plan to bring smoke alarms up to new-home placement, plus CO alarms where the house has an attached garage or fuel-fired appliances.
  • Watch the LARA Currently Open Rules page for changes to the court stay.

Sources: R 408.30500–408.30547g · LARA code books · LARA Currently Open Rules · 2022-16 LR tracker