Michigan’s plumbing venting rules come from the 2021 International Plumbing Code as amended in Part 7 of the Construction Code. Houses follow the residential code instead. The 2024 IPC adoption is still waiting to be filed — it is not the code in force today.
Why it matters
- Current rules adopt the international plumbing code, 2021 second printing (with listed Michigan exceptions) as the Michigan Plumbing Code (R 408.30701).
- Amended section 101.2 sends detached 1- and 2-family dwellings and townhouses not more than three stories with separate means of egress, and their accessory structures, to the Michigan Residential Code for plumbing (R 408.30711, section 101.2). Use that residential text for house jobs.
- Rule set 2025-8 LR would move Michigan to the 2024 IPC. As of Nov 5, 2026, its Filing date and Effective date are both Pending (final rules and JCAR package are posted). It takes effect 120 days after filing once filed. Until then, design and inspect to the 2021 IPC as amended.
Where to read the adopted IPC text
Michigan’s Admin Code states the amendments and which model-code sections are adopted or excepted. For the model IPC wording Michigan did not rewrite — including Chapter 3 pipe support / hanger provisions — use the free ICC Digital Codes Michigan viewer named on MCB’s resources list (codes.iccsafe.org/codes/united-states/michigan) or buy the book through LARA’s code-books channel referenced in R 408.30701. The Michigan amendments below are quoted from the Admin Code PDF.
Trap-to-vent distance and fixture-drain vents
Michigan amends IPC section 909.1:
- 909.1 Distance of trap from vent. Each fixture trap shall have a protecting vent located so that the slope and the developed length in the fixture drain from the trap weir to the vent fitting are within the requirements in table 909.1 (R 408.30723).
Michigan amends section 909.2:
- 909.2 Venting of fixture drains. The vent for a fixture drain, except where serving a fixture with integral traps such as water closets, shall connect above the weir of the fixture trap being vented. The total slope shall not exceed the diameter of the fixture drain (R 408.30725c).
Use table 909.1 from the adopted 2021 IPC for the developed-length numbers; Michigan points to that table rather than reprinting it in the Admin Code.
Combination waste and vent
Michigan adds section 915.1:
- A combination waste and vent system shall not serve fixtures other than floor drains, sinks, lavatories and drinking fountains. Combination waste and vent systems shall not receive the discharge from a food waste disposer or clinical sink (R 408.30725d).
Roof terminations and frost closure
Michigan’s roof and exterior vent amendments:
- 903.1 Roof extension. Open vent pipes through a roof terminate at least 1 foot (305 mm) above the roof, except that if the roof is used for any purpose other than weather protection, vent extensions run not less than 7 feet (2134 mm) above the roof (R 408.30753a).
- 903.1.1 Roof extension unprotected. Open vent pipes through a roof terminate not less than 12 inches (304.8 mm) above the roof (R 408.30753b).
- 903.2 Frost closure. To prevent frost closure, every vent extension through a roof shall be a minimum of 3 inches (76 mm) in diameter. Any increase in vent size shall be made inside the building a minimum of 1 foot (305 mm) below the roof or inside the wall (R 408.30754a).
- 903.7 Extensions outside a structure. Vent pipes installed on the exterior of the structure shall be protected against freezing by insulation or heat, or both (R 408.30754b).
Hanger and pipe-support spacing
Part 7’s Michigan amendments reviewed Nov 5, 2026 do not rewrite the IPC pipe-hanger or support spacing tables. Those spacing rules remain the adopted 2021 IPC text (commonly Chapter 3 general regulations / pipe support). Do not treat trade-press summaries as the Michigan rule. Open the adopted IPC in the ICC Michigan free viewer or the purchased Michigan Plumbing Code book, and follow any jobsite instructions from the enforcing agency.
What to do
- On commercial and multifamily work under the Michigan Plumbing Code, apply the Michigan amendments above first, then the rest of the 2021 IPC as adopted.
- On 1- and 2-family houses, switch to the Michigan Residential Code plumbing chapters (101.2).
- Watch the 2025-8 LR tracker for a filing date before you train crews on 2024 IPC venting changes.
Sources: R 408.30701–30796 · 2025-8 LR tracker · ICC Digital Codes: Michigan
Want a free sample issue? Sign up for the free sample. Pick your trades and we’ll email you the sample PDF.
Related
- Michigan Plumbing Code is moving to the 2024 IPC: where it stands
- What’s new in the 2024 IPC (and what Michigan might keep)
- Residential code on hold: what it means for plumbing on houses
More for Plumbing contractors: Michigan Plumbing updates.
Michigan Code Brief · Not legal advice. Every fact links to its official source. Checked Nov 5, 2026. Confirm with LARA or your local building department before you act.