Michigan mechanical code ventilation and exhaust: what Michigan changes

Written by

in

For ventilation on commercial and multifamily work, Michigan uses the 2021 International Mechanical Code (IMC) Chapter 4 as published. Michigan doesn’t rewrite any of it. Where Michigan does change things is on the exhaust side: where exhaust and dryer ducts can terminate, how dryer ducts are supported, and how kitchen hoods are tested. Houses follow the Michigan Residential Code, which has its own exhaust amendments. A pending 2024 IMC rule set would drop the commercial exhaust amendments. Here’s what is in force as of Nov 19, 2026 and what’s pending.

Which code covers ventilation

  • The Michigan Mechanical Code is the 2021 IMC, adopted by reference except for a short list of sections (R 408.30901a). None of the excluded sections are in Chapter 4 (Ventilation), and none of Michigan’s Part 9A amendment rules change a Chapter 4 section, so the 2021 IMC ventilation text applies as written (R 408.30901–408.30998).
  • LARA lists the 2021 Michigan Mechanical Code as current, effective March 12, 2024, and notes that “Residential requirements are contained in the Michigan Residential Code” (LARA code books).
  • Michigan adds a definition of “occupiable space” to the code: a room or enclosed space designed for human occupancy where people gather or work, “equipped with means of egress, heat, light, and ventilation facilities.” It doesn’t include spaces meant mainly for other uses, such as storage rooms and equipment rooms (R 408.30905a).

Michigan exhaust amendments (commercial, in force)

Michigan rewrites IMC sections 501.3, 504.4 and 504.9.2 (R 408.30945a):

  • Exhaust discharge (501.3): exhaust air must go outdoors where it won’t cause a public nuisance and can’t readily be drawn back in by a ventilating system. “Air shall not be exhausted into an attic or a crawl space, be directed onto walkways, or terminate within 3 feet of a ventilated section in a soffit.” Exceptions: whole-house attic fans in dwelling units with private attics, commercial cooking recirculating systems, and listed and labeled domestic ductless range hoods installed per the manufacturer’s instructions where Chapter 4 ventilation is otherwise provided.
  • Dryer exhaust termination (504.4): terminate outside the building, not within 3 feet of a ventilated soffit section, with a back-draft damper and no screen. Don’t use sheet metal screws or other fasteners that block the airflow, and don’t connect the duct to a vent connector, vent or chimney.
  • Dryer duct support (504.9.2): support and secure dryer exhaust ducts every 4 feet, install the insert end in the direction of airflow, and use no screws or fasteners that stick into the duct.

Kitchen hoods: Michigan’s capture and containment test

Michigan adds section 507.6.1.1. The field capture and containment test in 507.6.1 must follow the Bureau of Construction Codes’ smoke testing procedures, which are free from the bureau (R 408.30935a).

Permits

Michigan’s permit exemption list includes “portable ventilation appliances and equipment.” Fixed ventilation and exhaust systems aren’t on that list (R 408.30906a, section 106.2(b)).

Houses: Michigan Residential Code exhaust rules

One- and two-family homes fall under the 2015 Michigan Residential Code, which is still in effect under the court stay on the 2021 update (LARA Currently Open Rules). Its Michigan amendments (R 408.30500–408.30547g):

  • Exhaust openings (R303.5.2, R 408.30544): not directed onto walkways, not within 3 feet of a ventilated soffit section, and located so they don’t create a nuisance.
  • Dryer duct termination (M1502.3, R 408.30507): outside the building and per the dryer manufacturer’s instructions. If the instructions don’t say where, at least 3 feet in any direction from openings into buildings or a ventilated soffit section. A backdraft damper is required and a screen isn’t allowed.
  • Dryer duct support (M1502.4.2, R 408.30541a): supported at 4-foot intervals, insert end in the direction of airflow, and no screws that stick into the duct.

Pending: the 2024 IMC rule set

The 2025-7 LR tracker still shows Filing date: Pending and Effective date: Pending as of Nov 19, 2026. The rules take effect 120 days after filing. The final rule language would:

  • adopt the 2024 IMC, with appendices A, D and E as permissive guidelines only
  • rescind R 408.30945a, the Michigan exhaust and dryer amendments above, along with R 408.30947b
  • keep the “occupiable space” definition
  • amend 1109.3.2: refrigerant pipe shafts with A2L or B2L systems must be naturally or mechanically ventilated, and shafts with any A2, A3, B2 or B3 system must be continuously mechanically ventilated with a refrigerant detector. Detector-activated ventilation must start at no more than 25% of the refrigerant’s lower flammable limit.

None of this is in force until the tracker shows a filing date. Until then, follow the 2021 rules above.

What to do

  • For commercial ventilation rates and Chapter 4 requirements, work from the 2021 IMC text. Michigan doesn’t change it.
  • Keep exhaust and dryer terminations at least 3 feet from ventilated soffits, out of attics and crawl spaces, and off walkways. Support dryer ducts every 4 feet.
  • Get the BCC smoke test procedure before a commercial hood test.
  • Watch the 2025-7 LR tracker for a filing date.

Sources: R 408.30901–408.30998 · R 408.30500–408.30547g · LARA code books · LARA Currently Open Rules · 2025-7 LR tracker