If you install or alter boilers in Michigan (outside the residential carve-outs), you need a boiler license and a state boiler permit before the work starts. This page covers how to get licensed — not how to renew. Renewals are every Dec 31; see the related renewal post below.
Why it matters
- LARA’s boiler permit page states that installation and repairs of boilers and high-pressure piping may be done only by persons licensed by the Boiler Section, and that permits will not be issued to unlicensed persons (LARA boiler permit information).
- Under the Skilled Trades Regulation Act, a person shall not install or alter a boiler without first obtaining a permit from the boiler division. You are not eligible for that permit if you are not licensed under the boiler article, and unlicensed individuals may perform permit work only under the immediate supervision of a licensee (MCL 339.5939).
- The boiler article does not apply to certain boilers, including steam or vapor boilers at not more than 15 psig in a private residence or in an apartment of fewer than six families, and hot-water boilers at not more than 160 psig or 250°F in those same locations, plus other listed exemptions such as agricultural and federal-control boilers (MCL 339.5915). If the boiler is outside that list, plan on licensing and permits.
Installer and repairer experience (rules in force)
Current skilled-trades rules require a boiler installer or repairer license as required by MCL 339.5939 (R 339.5173):
- Installer: at least 5 years of experience in all phases of boiler installation in the class you are applying for. Up to 2 years credit may be given for 2 years of experience in the design, construction, manufacture or inspection of boilers.
- Repairer: at least 5 years of experience in all phases of boiler repair in that class. Up to 3 years credit may be given for 3 years of design, construction, manufacture or inspection experience.
LARA’s pathway page adds: submit an application and fee, get approved to test, then pass the exam; hold your current boiler license at least one year before upgrading classifications (LARA pathway to licensure). Written license exams require a score of 75% (R 339.5114). PSI administers installer/repairer exams after LARA approval; pay exam fees to PSI when you schedule (LARA boiler licensing page).
Installer classes
Class scope is in R 339.5174 and restated on LARA’s boiler licensing page:
- 1B: low-pressure boiler not exceeding 1,000,000 BTU/hour firing rate (modular sum also capped at that rate)
- 2B: low-pressure boiler of any capacity or firing rate, plus 1B work
- 3B: power boiler ≤ 5,000 lb steam/hour; install/replace non-boiler external piping (ASME B31.1 / R 339.5209); plus 2B work
- 4B: power boiler ≤ 300,000 lb steam/hour; non-boiler external piping; plus 3B work
- 5B: power boiler of any capacity except nuclear heat source; non-boiler external piping; plus 4B work
- 6B: nuclear heat-source boiler (extra federal/ASME evidence required)
- P: install or replace (and, for repairer P, repair) non-boiler external piping only
Repairer classes
From R 339.5175:
- I: repair a low-pressure boiler by means other than welding, riveting or other fabrication
- II: repair low-pressure, hot-water supply and fire-tube boilers of any pressure; plus Class I
- III: repair high-pressure boilers; repair or replace non-boiler external piping; plus Class II
- IV: repair or field-erect a boiler of any pressure except nuclear heat source; non-boiler external piping
- V: erect and repair nuclear heat-source boilers (ASME N-type stamp evidence required)
- P: non-boiler external piping only
Match the class to the boiler you will actually work on before you apply.
Fees (current rules)
R 339.5176 sets installer and repairer license, examination and renewal fees at $100 each. Permit application fees in the same rule include $100 for a low-pressure installation permit and $130 plus $0.06 per foot of piping for a high-pressure installation permit, among others. Apply online through Accela when you can (LARA boiler permits; aca-prod.accela.com/LARA).
Pending rules (not in force)
Two related rule sets still show Filing date: Pending and Effective date: Pending as of Nov 5, 2026:
- Boiler Code rewrite — 2025-64 LR tracker (final rules + JCAR package posted; takes effect 90 days after filing once filed)
- Skilled Trades Regulation Rules rewrite — 2025-58 LR tracker (same status). Its final R 339.5173 text would require “not less than 5 years and 10,000 hours” of experience with notarized employer statements. That hour figure is not in the Admin Code in force today; treat it as pending until the tracker shows a filing date.
What to do
- Confirm whether MCL 339.5915 takes the boiler out of the article. If not, pick the installer or repairer class that matches the equipment.
- Document your five years in that class, apply through LARA/Accela, then schedule PSI.
- Do not start install or alteration work until the boiler division issues the permit (MCL 339.5939).
Sources: MCL 339.5915 · MCL 339.5939 · R 339.5101–5412 · LARA boiler licensing · LARA boiler permits · 2025-64 LR · 2025-58 LR
Want a free sample issue? Sign up for the free sample. Pick your trades and we’ll email you the sample PDF.
Related
- Boiler licenses renew by December 31
- Michigan rulemaking roundup: Boiler Code and Skilled Trades rules
- Michigan mechanical contractor license: classifications and requirements
More for HVAC/Mechanical contractors: Michigan HVAC/Mechanical updates.
Michigan Code Brief · Not legal advice. Every fact links to its official source. Checked Nov 5, 2026. Confirm with LARA or your local building department before you act.