Short version: there’s a federal leak repair rule for HFC systems, and it’s been live since January 1, 2026. Most of your residential changeouts aren’t covered. Your commercial refrigeration customers probably are.
What the rule is
It’s part of EPA’s Emissions Reduction and Reclamation rule, written under the AIM Act. The citation is 40 CFR Part 84, Subpart C, and the leak section is 84.106. It covers appliances with a full charge of 15 pounds or more of an HFC refrigerant, or of a substitute with a GWP above 53.
Don’t mix it up with the older Section 608 rule. That one uses a 50 lb threshold and covers ozone-depleting refrigerants like R-22. It still exists. This is a second, separate rule aimed at HFCs.
What’s NOT covered
This matters most for a shop like ours. EPA’s fact sheet says appliances in the residential and light commercial air conditioning and heat pump subsector are not covered by these leak repair requirements. Your typical 3-ton split system in a Benton Harbor ranch house isn’t in scope. Neither are systems running refrigerants with a GWP of 53 or below.
What IS covered
Think walk-in coolers and freezers, reach-in rack systems, supermarket systems, process chillers, and larger commercial comfort-cooling equipment. Anything 15 lb or more on an HFC like R-404A, R-134a or R-410A, outside the residential/light-commercial AC subsector.
How it works on a service call
- Every time you add refrigerant to a covered appliance, the owner has to calculate a leak rate. The rule names a few exceptions: right after a retrofit, a new install, or a seasonal variance.
- If the leak rate is over the threshold, the clock starts. The thresholds are 30% for industrial process refrigeration, 20% for commercial refrigeration, and 10% for everything else.
- The leak has to be found and repaired within 30 days, or 120 days if an industrial process shutdown is needed.
- Verification tests confirm the fix.
Example: you top off a restaurant’s walk-in. It holds 22 lb of R-404A. You add 6 lb. Annualized, that’s well over 20%. The owner now has 30 days to get it fixed. Your job is to tell them, document it, and quote the repair.
Paperwork
Whoever adds or removes refrigerant has to give the owner documentation. That covers the appliance and its location, the date, the parts worked on, the type of service, the tech’s name, and the refrigerant type and amount. The owner keeps these records for at least three years. Full-charge records are kept until three years after the unit is retired. Owners also had to determine the full charge of every covered appliance by Jan 1, 2026, or at installation for newer units.
Reports go to EPA in some cases: extension requests, retrofit or retirement plans, and chronic leakers (more than 125% of full charge lost in a calendar year).
What to do this month
- Sort your commercial customers into “15 lb+ HFC” and “not covered.”
- Add charge size, refrigerant added and leak rate fields to your service ticket.
- Explain the 30-day clock to the owners. Most have never heard of it.
Still moving
In May 2026 EPA proposed exempting road and shipping-container transport refrigeration units. That doesn’t touch typical HVAC work. We found no proposal to change the 15 lb threshold itself.
Sources: EPA leak repair fact sheet · 40 CFR 84.106 · EPA reporting resources