New residential and light-commercial equipment has moved to A2L refrigerants, mainly R-454B and R-32. Here’s what EPA says, and where its guidance stops.
What “A2L” means
It’s an ASHRAE Standard 34 safety class. The “A” means lower toxicity. “2L” means lower flammability: it can burn, but less readily than an A2 or A3 like propane. EPA’s refrigerant safety page uses the ASHRAE 34 classes.
EPA’s rules (SNAP)
- SNAP Rule 23 listed R-452B, R-454A, R-454B, R-454C and R-457A as acceptable, subject to use conditions, for new residential and light-commercial AC and heat pumps. R-32 is listed the same way for that equipment, other than self-contained room ACs.
- EPA says A2L listings in Rules 23 and 25 require compliance with UL 60335-2-40 Edition 3. Edition 4 equipment is OK to the extent it also meets Edition 3.
- Charge size: to comply, you must use charge sizes that meet Edition 3, even where Edition 4 allows something different.
- Labels: both the red GHS flame diamond and the yellow ISO 7010-W021 triangle are consistent with EPA rules.
- EPA says following ASHRAE Standard 15 “will ensure the safety of technicians and building occupants.”
Practical habits (general safety, per EPA)
- Find and fix leaks promptly. Use leak detectors to warn of rising concentrations.
- Keep exposures low, and check the SDS for each refrigerant.
- Respect flammability limits. Control ignition sources where refrigerant could collect.
- Install per the manufacturer’s instructions. A2L equipment often has sensors and mitigation built in.
Michigan’s A2L rule
Michigan already allows A2L systems. The current Michigan Mechanical Code, in effect since March 12, 2024, says “System using A2L refrigerants shall comply with ASHRAE 15” and adopts the 2022 edition of ASHRAE 15 (Mich. Admin. Code R 408.30947b and R 408.30901). Houses fall under the Michigan Residential Code, so ask your inspector how they apply it there.
Not covered here
- Specific tool and recovery-equipment rules for A2Ls.
- Training or certification beyond EPA 608.
Check the manufacturer, your distributor’s training and your inspector on these.
Example
You’re quoting your first R-454B heat pump in a small basement mechanical room. Read the installation manual’s minimum room area and charge section before you quote. If the unit needs a mitigation board or sensor, that’s part of the job.
Sources: EPA SNAP Q&A · EPA SNAP Rule 23 fact sheet · EPA refrigerant safety · EPA restrictions by sector
Related
- R-410A: the federal install deadline is gone
- Michigan Mechanical Code is moving to the 2024 IMC
- EPA’s 15 lb HFC leak rule: what it means for a small Michigan shop
More for HVAC/Mechanical contractors: Michigan HVAC/Mechanical updates.
Michigan Code Brief · Not legal advice. Every fact links to its official source. Checked Oct 15, 2026. Confirm with LARA or your local building department before you act.